Daylight, Sunlight and Amenity

BS EN 17037 daylight targets against BRE guidance

8 min readBy PlanScope Editorial Team

One standard measures illuminance inside your new flats. The other measures obstruction at the neighbour's window. Schemes pass one and fail the other, so both belong in the submission.

BS EN 17037 daylight targets and the tests in BRE 209 answer different questions, which is why running one and presenting it as an answer to the other causes so much trouble at planning stage. BS EN 17037:2018 with its UK National Annex tells you whether the rooms in your new building receive enough daylight. BRE 209 (2022) tells you what your building does to the daylight and sunlight reaching buildings and spaces around it. A scheme can pass one and fail the other, and frequently does.

The 2022 edition of BRE 209 made the relationship closer by adopting the BS EN 17037 approach for assessing daylight in new interiors, replacing the average daylight factor targets that the 2011 edition used. That change removed one source of confusion and created another.

Two documents written for different questions

BRE 209 is a site layout guide. Its central tests measure obstruction: the vertical sky component at a point on the outside face of a window, the no-sky line inside a room, annual probable sunlight hours at a window, and sun on the ground in gardens and amenity areas. All of those are computed from geometry, and all of them are designed to compare a before case with an after case.

BS EN 17037 is a performance standard for the inside of a space. It asks whether a target illuminance is reached over a defined fraction of the reference plane for a defined fraction of daylight hours. It has nothing to say about the neighbour, and it cannot be used to measure a loss.

So the division of labour is simple. If the question is whether the proposed flats are habitable, that is BS EN 17037 as adopted by BRE 209 for new interiors. If the question is what happens to number 24 next door, that is the vertical sky component test and the 27 per cent benchmark and its companions.

Target illuminance and the fraction of the space

BS EN 17037 sets recommended target illuminance levels to be achieved over at least half the reference plane for at least half the daylight hours in the year, with a minimum level to be met over almost the whole plane.

The UK National Annex reduces the targets for dwellings to reflect the British climate and existing housing stock:

Space UK National Annex target illuminance
Bedroom 100 lux
Living room 150 lux
Kitchen 200 lux

Those figures are achieved over 50 per cent of the reference plane for at least half of daylight hours. The reference plane itself matters as much as the number: it sits at working plane height, inset from the walls by a stated margin, and a modeller who changes the inset changes the result.

Notice what the criterion rewards. Glazing area, glazing transmittance, internal surface reflectance and room depth all move the answer, so a designer can recover a poorly obstructed room by making the window bigger. That is a real design lever, and it is also the reason the standard cannot police the effect on the neighbour.

Climate-based daylight modelling explained plainly

The illuminance criterion is time-based, so it needs a year of sky conditions rather than a single overcast sky. Climate-based daylight modelling runs the room geometry against hourly climate data for the nearest representative location, producing an illuminance value at every point on the reference plane for every hour, then reports the fraction of hours the target is met.

The practical consequences for a planning submission are worth stating in the report.

  • The weather file is an input. Name it, name the location it represents, and say which year or which typical-year dataset it uses.
  • Orientation now matters. Two identical rooms facing north and south give different results, which the old daylight factor method could not show.
  • Run time and output size are larger, so the modelling sits earlier in the programme than a geometric assessment would.
  • The result is sensitive to reflectance assumptions. State the values used for walls, floors, ceilings and any external surfaces, and use realistic rather than aspirational figures.

BS EN 17037 also permits a simplified route using daylight factors, with a target daylight factor derived from the target illuminance and the local climate. It is quicker and it is accepted, but it loses the orientation sensitivity that makes the climate-based method useful. Where a scheme is marginal, run the climate-based method and say why.

The term spatial daylight autonomy comes from other rating systems and describes a similar idea, a percentage of the area meeting a lux target for a percentage of occupied hours. Use the BS EN 17037 wording in a planning report and reserve the other term for the rating scheme it belongs to, or you invite a query about which criterion you actually tested.

Which document local policy points to

Most adopted local plans still refer to BRE guidance in general terms, without naming an edition. That works in your favour and against you at the same time: it allows the 2022 edition to be used, and it leaves an objector free to argue for the 2011 targets.

A minority of authorities, mostly in London and in other dense urban areas, set out their own approach in a supplementary planning document or design guide, sometimes with alternative daylight targets calibrated to local context. Where that exists it takes priority over the generic reference, and the argument shifts from method to local policy compliance. The way those context-based targets work is set out under alternative daylight targets in dense urban areas.

Read the local plan policy, the validation list and any design guide before scoping the assessment. Then say in the report which document you are testing against and why. An assessment that silently picks the more favourable framework is the one that gets challenged.

Running both and reporting the difference

On any scheme with new residential accommodation and neighbouring residential property, you need both analyses, and they belong in separate chapters with separate assumptions.

The internal assessment covers every habitable room in the proposal, reports illuminance results against the National Annex targets by room type, and identifies the rooms that fall short with the reason: depth, obstruction, balcony overhang or orientation. The external assessment covers neighbouring windows and amenity spaces using the BRE 209 geometric tests, with existing and proposed values side by side.

Then write a short reconciliation. Where the proposal creates rooms that meet the internal targets only because of large glazed areas, say so, because the same glazing drives the overheating risk assessment under Part O and the two analyses have to be consistent. A scheme that solves daylight with glass and then solves overheating with shading has to model the shading in the daylight run.

Where the two give opposite answers

Three combinations come up regularly.

A tall proposal on a tight urban site can meet every internal target, because the flats have generous full-height glazing, while cutting the vertical sky component at the neighbouring terrace well below the 0.8 relative threshold. The internal results are irrelevant to that harm, and presenting them as mitigation reads as evasion.

A low-rise scheme that respects every neighbour can produce single-aspect flats behind deep balconies that fail the 150 lux living room target over half the plane. Here the obstruction tests pass and the habitability argument is the weak point, which is the harder case to defend at appeal because it concerns the future occupiers of the applicant's own building.

And a refurbishment that keeps existing window openings can fail the internal targets outright while causing no external harm at all. Where the existing building is listed or in a conservation area and the openings cannot change, the honest report says the targets cannot be met, explains why, and relies on the flexibility that both documents allow for existing buildings and constrained sites. The 2022 edition's treatment of that flexibility is covered under the BRE 209 changes for new interiors.

What to put in front of a case officer

Case officers are rarely daylight specialists, so the structure of the report does more work than the modelling. Four things belong at the front.

  1. A one-page statement of which document applies to which question, with the edition and the National Annex named.
  2. A table of internal results by room type against the target illuminance, with the failing rooms listed and explained.
  3. A table of external results by property, with existing and proposed values and the relative ratio.
  4. A plain statement of the residual effects and the reason they are acceptable in this context, referring to the local policy wording.

Keep the model settings, weather file, reflectances and reference plane definitions in an appendix. A daylight and sunlight assessment that buries its assumptions is the one an objector's consultant takes apart, and the recovery costs more than getting the appendix right in the first place.

Councils normally expect this work to be done by someone experienced in both frameworks, and professional review before submission is strongly advised. PlanScope drafts the report structure, the methodology narrative and the policy framing, and marks every figure it cannot source as to be confirmed. Enter your postcode to see which reports your site is likely to need.

PlanScope provides AI-assisted draft reports for planning applications. Reports should be reviewed before submission. We do not guarantee planning approval.

Frequently asked questions

What are the UK National Annex daylight targets in BS EN 17037?

For dwellings the National Annex sets target illuminance of 100 lux in bedrooms, 150 lux in living rooms and 200 lux in kitchens, to be achieved over 50 per cent of the reference plane for at least half of daylight hours. The reference plane position and inset from the walls affect the result, so both should be stated.

Did BRE 209 (2022) replace average daylight factor?

Yes, for assessing daylight in new interiors. The 2022 edition adopts the BS EN 17037 illuminance approach in place of the average daylight factor targets used in the 2011 edition. The obstruction tests for effects on existing buildings, including vertical sky component, no-sky line and annual probable sunlight hours, remain.

Can BS EN 17037 be used to assess loss of light to a neighbour?

No. It is a performance standard for daylight provision inside a space and has no mechanism for comparing a before case with an after case at someone else's window. Loss of light to neighbouring property is assessed with the BRE 209 geometric tests, and presenting good internal results as mitigation for external harm reads badly.

What is climate-based daylight modelling?

It runs the room geometry against hourly climate data for a representative location, giving illuminance at every point on the reference plane for every hour of the year, then reports the fraction of hours meeting the target. Unlike the daylight factor method it responds to orientation, so the weather file and reflectance assumptions must be named in the report.

Which framework does local policy require?

Most adopted local plans refer to BRE guidance without naming an edition, which allows the 2022 edition to be used. Some authorities, mainly in dense urban areas, publish their own approach or alternative targets in a design guide or supplementary planning document, and that takes priority. Check the policy and validation list before scoping.

Sources and further reading

daylightbs en 17037bre 209amenityarchitectsilluminance

This article is general guidance about the planning system in England and, where stated, the rest of the UK. It is not legal or professional advice. Check your local planning authority’s validation requirements and take professional advice for your specific site.

More in Daylight, Sunlight and Amenity

View all →
Daylight, Sunlight and Amenity6 min read

Daylight to rooms behind deep balconies and access decks

The obstruction is your own building. How projection, soffit height and balustrade choice change the daylight result, and what the assessment has to show.

Read article →
Daylight, Sunlight and Amenity8 min read

Adequate natural light as a Class MA prior approval matter

Adequate natural light carries a duty to refuse, not a discretion to weigh, and it is assessed on your drawings. Here is what to submit and how deep floorplates are made to work.

Read article →
Daylight, Sunlight and Amenity7 min read

Overshadowing of a public park by a tall building

The sun on ground test gives one number for an amenity space. A park is many spaces. Here is how to zone it, baseline it and report it so the result survives committee.

Read article →
Daylight, Sunlight and Amenity7 min read

Obscure glazing conditions and their daylight effect

Obscuring glass leaves the geometric daylight metrics untouched and alters everything calculated from transmittance. What changes, what does not, and the alternatives.

Read article →
Daylight, Sunlight and Amenity8 min read

Amenity harm and the presumption in favour of development

A failed Vertical Sky Component test is an input, not a reason for refusal. How to turn daylight findings into weight an inspector can use in the planning balance.

Read article →
Daylight, Sunlight and Amenity7 min read

Measuring existing windows for a daylight survey

External geometry can be measured from the street. Room depth and room use cannot, and that is where most daylight assessments are challenged at committee and on appeal.

Read article →