Noise, Air, Odour and Light

Lighting design where bats are present

7 min readBy PlanScope Editorial Team

All UK bat species are European protected species, so a lighting layout on a site with bats is an ecological document first. What the plan must show and how the condition should be worded.

Lighting a roost access point or the hedgerow a colony commutes along can amount to an offence, which is why a lighting design on a site with bats is an ecological document before it is an engineering one. All bat species in the UK are European protected species under the Conservation of Habitats and Species Regulations 2017, and the offences include deliberate disturbance and damaging or destroying a breeding site or resting place. A light that makes a roost exit unusable can engage both.

For a reviewer, the test is whether the lighting design and the ecological mitigation describe the same site. They often do not, because the lighting layout is produced by one consultant from a site plan and the dark corridors by another from a survey drawing, and nobody overlays them.

Why artificial light matters to bats

Three mechanisms, each with a different design response.

Illumination of a roost access point delays or prevents emergence. Bats leave at a time tied to light levels, and a lit exit pushes emergence later, shortens the foraging period and in some cases causes abandonment. This is the mechanism most likely to constitute an offence.

Illumination of a commuting route fragments it. Light-averse species will not cross a lit gap, so a lit stretch of hedgerow becomes a barrier, severing a colony from its foraging ground even though no habitat has been removed.

And lighting alters prey availability. Insects are drawn to short wavelength light, which concentrates prey at luminaires and depletes it elsewhere. Tolerant species feed at the light, which exposes them to predation and traffic, while sensitive species lose the resource altogether.

Species sensitivity and foraging behaviour

Sensitivity is not uniform, and the mitigation target should follow the species recorded rather than a generic figure.

Slow-flying, cluttered-habitat species are the most light-averse: horseshoe bats, the Myotis group, long-eared bats and barbastelle. These species hug vegetation, emerge late and avoid illumination strongly. Where any of them is recorded, the design has to achieve near-baseline conditions along the features they use.

Faster, open-air species including the pipistrelles, noctule and serotine are more tolerant and will forage around lights. That tolerance is not a licence to light. Feeding at a luminaire is a behavioural change with its own costs, and a scheme that relies on it in mitigation terms will be challenged.

Which species are present is a question for survey, not inference, and the survey work and any mitigation licence require a suitably licensed ecologist under the 1981 Act and the 2017 Regulations. A licensed or competent professional is legally required for that work, and an AI-assisted draft is a starting point for that professional rather than a substitute for the survey.

Keeping hedgerows and watercourses dark

The core of the mitigation is a dark corridor: a continuous unlit or near-unlit route linking roosts to foraging habitat, following hedgerows, treelines, watercourses and woodland edges.

Design rules that hold up in review:

  • Keep the corridor continuous. A single lit crossing point breaks it, and a 10 metre gap can be as damaging as lighting the whole length.
  • Set the target at the vertical face of the feature, not at ground level in the middle of the road. A figure commonly adopted in practice is a maximum of 1 lux at the hedgerow or bank face, with the project ecologist setting the value for the species present.
  • Keep the feature itself and a buffer out of the lit area, rather than lighting up to the edge of it.
  • Where a road must cross a corridor, consider a short unlit section, a hop-over of retained canopy, or an underpass, and model the spill from the nearest luminaires either side.
  • Do not rely on planting as a screen unless it is evergreen and established, because a deciduous hedge screens nothing in March when bats become active again.

Retention of the linear features themselves is the first move, and the arguments for keeping hedgerows and treelines in a layout are the same ones made for trees and green infrastructure in other contexts.

Luminaire choice, spectrum and shielding

Spectrum first. Warm sources with a correlated colour temperature at or below 2700 K reduce the short wavelength content that attracts insects and disturbs bats most, and LED sources should carry no ultraviolet output. A 4000 K source specified for perceived safety is the most common conflict with an ecological condition, and it is worth settling with the highway authority before the layout is agreed.

Then geometry. A full cut-off luminaire with a flat glass and no upward component, mounted as low as the lit task allows, with a directional optic aimed away from the retained feature. Lower columns with tighter spacing will usually beat taller columns at wider spacing for spill control, though they cost more. Accessories matter: louvres, side shields, hoods and baffles, specified by part number so that what is installed matches what was modelled.

Upward light has its own consequences beyond bats, and the discussion of sky glow and upward light ratio covers the overlap with dark skies policy where a site sits in or near a protected landscape.

Two details reviewers check. Whether bollard or low-level lighting has been used near a corridor, since bollards throw light sideways at exactly the height of a hedge base. And whether building-mounted lighting, security floodlights and illuminated signage have been included in the model, because they are frequently left out and frequently the worst offenders.

Timing controls and part-night lighting

Part-night lighting, switching off or dimming deeply through the core of the night, is effective where the highway authority will accept it. Align the regime with bat activity rather than with a standard template: the sensitive period runs from before sunset through to after sunrise, and activity through the season is highest from spring to autumn.

Passive infrared control needs care. A luminaire that jumps from off to full output as a bat or a person passes creates a sudden illumination event, which is disturbing in a different way from constant light. Where detection control is used, specify a dimmed standby level, a slow ramp and a short timeout, and keep detectors away from the corridor so that bat movement itself does not trigger them.

Record the control strategy in the lighting design rather than leaving it to commissioning. A scheme approved with a part-night regime and installed on a photocell with no timeclock has not delivered the mitigation.

What the lighting plan must show the ecologist

A reviewer cannot assess a lighting layout without the ecological constraints on the same drawing. Ask for a single plan carrying:

  1. The roosts, access points, commuting routes and foraging areas from the survey, with their status and the species recorded.
  2. The dark corridors, with the lux target at each feature stated on the drawing.
  3. Every light source: street lighting, building-mounted, car park, signage, bollards and any floodlighting, with the luminaire schedule.
  4. Isolux contours at ground level and, separately, at the vertical plane of each retained feature.
  5. Mounting heights, tilt, aiming direction and shielding accessories per luminaire type.
  6. Correlated colour temperature and the photometric file reference for each type.
  7. The control strategy with switching and dimming times.

Anything missing from that list is a gap in the assessment, not a detail for later. A Lighting Assessment prepared against the joint Bat Conservation Trust and Institution of Lighting Professionals guidance, in its current edition, is the document that pulls these together.

Conditions that can actually be enforced

Weak conditions are the usual failure point. "External lighting shall be designed to minimise impacts on bats" is unenforceable, because nobody can say whether it has been complied with.

Wording that works specifies the document, the numbers and the verification: approval of a lighting scheme designed by a competent lighting professional in consultation with the project ecologist, achieving a stated maximum illuminance at identified features, with named luminaire types, colour temperature, mounting heights, aiming and shielding, a defined switching and dimming regime, and a post-installation verification report confirming measured levels at those features. Add a limb preventing any change to type, position, height, aiming, colour temperature or controls without further approval.

Then check the verification report when it arrives. Measured levels at the hedgerow face, taken after dark with the installation at full output, with the instrument and its calibration date recorded, are what close the condition out. Where offences are likely despite mitigation, a licence from Natural England is a separate requirement and the mitigation licence application is the licensed ecologist's work.

This is general guidance, not legal advice; check the position with your local planning authority or a qualified professional before relying on it. For specialist technical reports, qualified professional input may be required.

To scope the ecological and environmental documents a site needs, enter your postcode on PlanScope and work through the constraints it detects. PlanScope provides AI-assisted draft reports for planning applications. Reports should be reviewed before submission. We do not guarantee planning approval.

Frequently asked questions

Can lighting a bat roost be an offence?

It can. Under the Conservation of Habitats and Species Regulations 2017 the offences include deliberate disturbance and damaging or destroying a breeding site or resting place. Illuminating a roost access point delays or prevents emergence and can render the roost unusable, which may engage both limbs. Survey and licensing are work for a licensed ecologist.

Which bat species are most sensitive to light?

Slow-flying species of cluttered habitats: horseshoe bats, the Myotis group, long-eared bats and barbastelle. They hug vegetation, emerge late and avoid illumination strongly. Pipistrelles, noctule and serotine are more tolerant and will forage at lights, but that is a behavioural change with costs rather than a reason to light a corridor.

What lux limit applies to a dark corridor?

There is no single statutory figure. A value commonly adopted in practice is a maximum of 1 lux at the vertical face of the hedgerow, bank or treeline, with the project ecologist setting the target for the species recorded. Measure or model at the feature itself rather than at ground level in the carriageway.

What colour temperature should be specified?

Warm sources at or below 2700 K, with no ultraviolet output from the LED. Short wavelength content attracts insects and disturbs bats most. A 4000 K specification requested for perceived safety is the most common conflict with an ecological condition, so settle it with the highway authority before the layout is fixed.

Is motion detection good or bad for bats?

It needs care. A luminaire jumping from off to full output creates a sudden illumination event that is disturbing in its own way. Where detection control is used, specify a dimmed standby level, a slow ramp and a short timeout, and keep the detectors away from the corridor so bat movement does not trigger them.

How should a bat lighting condition be worded?

Name the document, the numbers and the verification: a scheme by a competent lighting professional in consultation with the project ecologist, achieving a stated maximum illuminance at identified features, with luminaire types, colour temperature, heights, aiming, shielding and switching times, plus a post-installation measured verification report and a bar on changes without approval.

Sources and further reading

batslightingprotected speciesecologymitigationplanning conditions

This article is general guidance about the planning system in England and, where stated, the rest of the UK. It is not legal or professional advice. Check your local planning authority’s validation requirements and take professional advice for your specific site.

More in Noise, Air, Odour and Light

View all →
Noise, Air, Odour and Light7 min read

Statutory nuisance and why permission is no defence

Part III of the Environmental Protection Act 1990 contains no defence of holding planning permission. How abatement notices work, and what best practicable means requires of an operator.

Read article →
Noise, Air, Odour and Light6 min read

When vibration is assessed in a planning application

Human response and building damage thresholds differ by more than an order of magnitude, so the two assessments need separate sections and separate criteria.

Read article →
Noise, Air, Odour and Light7 min read

Predicting construction noise under BS 5228

Four inputs drive a BS 5228 construction noise prediction, and on-time percentages are the one most often got wrong. How the calculation and the criteria work.

Read article →
Noise, Air, Odour and Light7 min read

Delivery and servicing hours conditions on noise grounds

Delivery noise is short, loud events that a BS 4142 rating level dilutes, which is why authorities restrict hours instead. How to assess the events, mitigate them and negotiate the hours.

Read article →
Noise, Air, Odour and Light7 min read

Part O overheating against closed-window noise mitigation

Approved Document O rules out open windows above 40 dB LAeq at night, while acoustic conditions usually cite BS 8233's 30 dB. That 10 dB gap is where most urban infill sits, and it has to be resolved before submission.

Read article →
Noise, Air, Odour and Light7 min read

Vertical illuminance at a window and the curfew

Vertical illuminance at a neighbouring window decides most light trespass objections, and the limit drops after the curfew hour. How the calculation plane is set, which zone applies and what mitigation moves the figure.

Read article →